Модуль CPU 115SER,16 (20) входов, 16 (12) выходов, 32 кбайт рабочей памяти, 40 кбайт загрузочной памяти, 2-й интерфейс RS-232 (PtP), расширяемый, бесплатное ПО WinPLC7 Lite
Наименование
|
CPU 115 MicroPLC |
Тип
|
VIPA 115-6BL14 |
Габаритные размеры, В х Ш х Г, мм
|
152.4 mm x 76 mm x 48 mm |
Температура окружающей среды
|
0 °C .. 60 °C |
Серия
|
100V |
Поддерживаемые протоколы
|
MPI, Modbus Master/Slave |
Объем памяти
|
32 КБ |
Количество сигналов
|
DI 16(20)xDC 24В/ DO 16(12)xDC 24В |
|
LEDs
Label | Color | Description |
R | green | CPU is in the operating mode RUN. |
S | yellow | CPU is in the operating mode STOP. |
PW | green | Signalizes the started CPU. |
SF | red | Blinks at system errors (hardware defect) |
FC | yellow | Blinks, if variables are forced (fixed). |
MC | yellow |
Blinking shows accesses at the MMC. |
Interface
MP2I | Description | RS232 | Description | |||
|
|
Status monitor pin assignment
LED | Description | Pin assignment | |||
.0... .7 |
LEDs (green) |
|
*) At X3 parameterizable as counter res. alarm input.
LED | Description | Pin assignment | |||
L+ |
LED (green) |
|
|||
.0... .7 |
LEDs (green) |
||||
F |
LED (red) |
*) At X5 parameterizable as pulse output with max. output current of 0.5A per channel.
LED | Description | Pin assignment | |||
L+ |
LED (green) |
|
|||
.0... .3 |
LEDs (green) |
||||
.4... .7 |
LEDs (green) |
||||
F |
LED (red) |
|
*) At X5 parameterizable as pulse output with max. output current of 0.5A per channel.
Order no. |
115-6BL14 |
Type | CPU 115SER |
General information |
|
Note | - |
Features | 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 32 kB work memory, 40 kB load memory RS232 interface |
Technical data power supply |
|
Power supply (rated value) | DC 24 V |
Power supply (permitted range) | DC 20.4...28.8 V |
Reverse polarity protection | |
Current consumption (no-load operation) | 100 mA |
Current consumption (rated value) | 1 A |
Inrush current | 58 A |
I²t | 0.38 A²s |
Max. current drain at backplane bus | 0.8 A |
Power loss | 9 W |
Reverse polarity protection | |
Technical data digital inputs |
|
Number of inputs | 16 (20 |
Cable length, shielded | 1000 m |
Cable length, unshielded | 600 m |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | |
Current consumption from load voltage L+ (without load) | - |
Rated value | DC 24 V |
Input voltage for signal "0" | DC 0...5 V |
Input voltage for signal "1" | DC 15...28.8 V |
Input current for signal "1" | 7 mA |
Connection of Two-Wire-BEROs possible | |
Max. permissible BERO quiescent current | 1.5 mA |
Input delay of "0" to "1" | 3 ms |
Input delay of "1" to "0" | 3 ms |
Input characteristic curve | IEC 61131-2, type 1 |
Initial data size | 3 Byte |
Technical data digital outputs |
|
Number of outputs | 16 (12 |
Cable length, shielded | 1000 m |
Cable length, unshielded | 600 m |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | - |
Current consumption from load voltage L+ (without load) | 50 mA |
Total current per group, horizontal configuration, 40°C | 4 A |
Total current per group, horizontal configuration, 60°C | 4 A |
Total current per group, vertical configuration | 4 A |
Output voltage signal "1" at min. current | L+ (-125 mV) |
Output voltage signal "1" at max. current | L+ (-0.8 V) |
Output current at signal "1", rated value | 0.5 A |
Output delay of "0" to "1" | max. 100 µs |
Output delay of "1" to "0" | max. 350 µs |
Minimum load current | - |
Lamp load | 5 W |
Switching frequency with resistive load | max. 1000 Hz |
Switching frequency with inductive load | max. 0.5 Hz |
Switching frequency on lamp load | max. 10 Hz |
Internal limitation of inductive shut-off voltage | L+ (-52 V) |
Short-circuit protection of output | yes, electronic |
Trigger level | 1 A |
Output data size | 3 Byte |
Technical data counters |
|
Number of counters | 4 |
Counter width | 32 Bit |
Maximum input frequency | 30 kHz |
Maximum count frequency | 30 kHz |
Mode incremental encoder | |
Mode pulse / direction | |
Mode pulse | |
Mode frequency counter | - |
Mode period measurement | - |
Gate input available | |
Latch input available | - |
Reset input available | - |
Counter output available | - |
Status information, alarms, diagnostics |
|
Status display | yes |
Interrupts | yes |
Process alarm | yes |
Diagnostic interrupt | yes |
Diagnostic functions | no |
Diagnostics information read-out | possible |
Supply voltage display | green LED |
Group error display | red SF LED |
Channel error display | none |
Isolation |
|
Between channels of groups to | 8 |
Between channels and backplane bus | |
Insulation tested with | DC 500 V |
PWM data |
|
PWM channels | 2 |
PWM time basis | - |
Period length | - |
Minimum pulse width | - |
PtP communication | - |
Technical data power supply |
|
Power supply (rated value) | DC 24 V |
Power supply (permitted range) | DC 20.4...28.8 V |
Reverse polarity protection | |
Current consumption (no-load operation) | 100 mA |
Current consumption (rated value) | 1 A |
Inrush current | 58 A |
I²t | 0.38 A²s |
Max. current drain at backplane bus | 0.8 A |
Max. current drain load supply | - |
Power loss | 9 W |
Load and working memory |
|
Load memory, integrated | 40 KB |
Load memory, maximum | 40 KB |
Work memory, integrated | 32 KB |
Work memory, maximal | 32 KB |
Memory divided in 50% program / 50% data | - |
Memory card slot | MMC-Card with max. 512 MB |
Hardware configuration |
|
Racks, max. | 1 |
Modules per rack, max. | 4 |
Number of integrated DP master | - |
Number of DP master via CP | 4 |
Operable function modules | 4 |
Operable communication modules PtP | 4 |
Operable communication modules LAN | - |
Command processing times |
|
Bit instructions, min. | 0.25 µs |
Word instruction, min. | 1.2 µs |
Double integer arithmetic, min. | 2.6 µs |
Floating-point arithmetic, min. | 50 µs |
Timers/Counters and their retentive characteristics |
|
Number of S7 counters | 256 |
S7 counter remanence | adjustable 0 up to 64 |
S7 counter remanence adjustable | C0 .. C7 |
Number of S7 times | 256 |
S7 times remanence | adjustable 0 up to 128 |
S7 times remanence adjustable | not retentive |
Data range and retentive characteristic |
|
Number of flags | 8192 Bit |
Bit memories retentive characteristic adjustable | adjustable 0 up to 256 |
Bit memories retentive characteristic preset | MB0 .. MB15 |
Number of data blocks | 2047 |
Max. data blocks size | 16 KB |
Number range DBs | 1 ... 2047 |
Max. local data size per execution level | 1024 Byte |
Max. local data size per block | 1024 Byte |
Blocks |
|
Number of OBs | 14 |
Maximum OB size | 16 KB |
Total number DBs, FBs, FCs | - |
Number of FBs | 1024 |
Maximum FB size | 16 KB |
Number range FBs | 0 ... 1023 |
Number of FCs | 1024 |
Maximum FC size | 16 KB |
Number range FCs | 0 ... 1023 |
Maximum nesting depth per priority class | 8 |
Maximum nesting depth additional within an error OB | 1 |
Time |
|
Real-time clock buffered | |
Clock buffered period (min.) | 30 d |
Type of buffering | Vanadium Rechargeable Lithium Battery |
Load time for 50% buffering period | 20 h |
Load time for 100% buffering period | 48 h |
Accuracy (max. deviation per day) | 10 s |
Number of operating hours counter | 8 |
Clock synchronization | - |
Synchronization via MPI | - |
Synchronization via Ethernet (NTP) | - |
Address areas (I/O) |
|
Input I/O address area | 1024 Byte |
Output I/O address area | 1024 Byte |
Process image adjustable | - |
Input process image preset | 128 Byte |
Output process image preset | 128 Byte |
Input process image maximal | 128 Byte |
Output process image maximal | 128 Byte |
Digital inputs | 8192 |
Digital outputs | 8192 |
Digital inputs central | 148 |
Digital outputs central | 144 |
Integrated digital inputs | 16 (20 |
Integrated digital outputs | 16 (12 |
Analog inputs | 512 |
Analog outputs | 512 |
Analog inputs, central | 32 |
Analog outputs, central | 16 |
Integrated analog inputs | - |
Integrated analog outputs | - |
Communication functions |
|
PG/OP channel | |
Global data communication | |
Number of GD circuits, max. | 4 |
Size of GD packets, max. | 22 Byte |
S7 basic communication | |
S7 basic communication, user data per job | 76 Byte |
S7 communication | |
S7 communication as server | |
S7 communication as client | - |
S7 communication, user data per job | 160 Byte |
Number of connections, max. | 16 |
Functionality Sub-D interfaces |
|
Type | MP²I |
Type of interface | RS485 |
Connector | Sub-D, 9-pin, female |
Electrically isolated | - |
MPI | |
MP²I (MPI/RS232) | |
DP master | - |
DP slave | - |
Point-to-point interface | - |
Type | COM |
Type of interface | RS232 |
Connector | Sub-D, 9-pin, male |
Electrically isolated | - |
MPI | - |
MP²I (MPI/RS232) | - |
DP master | - |
DP slave | - |
Point-to-point interface | |
Functionality MPI |
|
Number of connections, max. | 16 |
PG/OP channel | |
Routing | - |
Global data communication | |
S7 basic communication | |
S7 communication | |
S7 communication as server | |
S7 communication as client | - |
Transmission speed, min. | 19.2 kbit/s |
Transmission speed, max. | 187.5 kbit/s |
Point-to-point communication |
|
PtP communication | |
Interface isolated | - |
RS232 interface | |
RS422 interface | - |
RS485 interface | - |
Connector | Sub-D, 9-pin, male |
Transmission speed, min. | 150 bit/s |
Transmission speed, max. | 115.2 kbit/s |
Cable length, max. | 15 m |
Point-to-point protocol |
|
ASCII protocol | |
STX/ETX protocol | |
3964(R) protocol | |
RK512 protocol | - |
USS master protocol | |
Modbus master protocol | |
Modbus slave protocol | |
Special protocols | - |
Housing |
|
Material | PPE / PA 6.6 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 152.4 mm x 76 mm x 48 mm |
Weight | 302 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL508 certification | yes |
Order no. | Name/Description | |
---|---|---|
112-4BH02 |
CPU 112 - Micro PLC 8 (12) inputs 8 (4) outputs 8 kB work memory, 16 kB load memory |
[Datasheet] [Manual] |
114-6BJ02 |
CPU 114 - Micro PLC 16 (20) inputs 8 (4) outputs from which are 2 PWM 50 kHz outputs 16 kB work memory, 24 kB load memory |
[Datasheet] [Manual] |
114-6BJ03 |
CPU 114 - Micro PLC 16 (20) inputs 8 (4) outputs from which are 2 PWM 50 kHz outputs 24 kB work memory, 32 kB load memory |
[Datasheet] [Manual] |
114-6BJ04 |
CPU 114 - Micro PLC 16 (20) inputs 8 (4) outputs from which are 2 PWM 50 kHz outputs 32 kB work memory, 40 kB load memory |
[Datasheet] [Manual] |
114-6BJ52 |
CPU 114R - Micro PLC 16 inputs 8 relay outputs AC 230 V/ DC 30 V 16 kB work memory, 24 kB load memory |
[Datasheet] [Manual] |
114-6BJ53 |
CPU 114R - Micro PLC 16 inputs 8 relay outputs AC 230 V/ DC 30 V 24 kB work memory, 32 kB load memory |
[Datasheet] [Manual] |
114-6BJ54 |
CPU 114R - Micro PLC 16 inputs 8 relay outputs AC 230 V/ DC 30 V 32 kB work memory, 40 kB load memory |
[Datasheet] [Manual] |
115-6BL02 |
CPU 115 - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 16 kB work memory, 24 kB load memory |
[Datasheet] [Manual] |
115-6BL03 |
CPU 115 - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 24 kB work memory, 32 kB load memory |
[Datasheet] [Manual] |
115-6BL04 |
CPU 115 - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 32 kB work memory, 40 kB load memory |
[Datasheet] [Manual] |
115-6BL12 |
CPU 115SER - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 16 kB work memory, 24 kB load memory RS232 interface |
[Datasheet] [Manual] |
115-6BL13 |
CPU 115SER - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 24 kB work memory, 32 kB load memory RS232 interface |
[Datasheet] [Manual] |
115-6BL14 |
CPU 115SER - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 32 kB work memory, 40 kB load memory RS232 interface |
[Datasheet] [Manual] |
115-6BL22 |
CPU 115DP - Micro PLC 16 (20) inputs 16 (12) outputs 16 kB work memory, 24 kB load memory PROFIBUS-DP slave interface |
[Datasheet] [Manual] |
115-6BL23 |
CPU 115DP - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 24 kB work memory, 32 kB load memory PROFIBUS-DP slave interface |
[Datasheet] [Manual] |
115-6BL24 |
CPU 115DP - Micro PLC 16 (20) inputs 16 (12) outputs 32 kB work memory, 40 kB load memory PROFIBUS-DP slave interface |
[Datasheet] [Manual] |
115-6BL32 |
CPU 115SER - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 16 kB work memory, 24 kB load memory RS485 interface |
[Datasheet] [Manual] |
115-6BL33 |
CPU 115SER - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 24 kB work memory, 32 kB load memory RS485 interface |
[Datasheet] [Manual] |
115-6BL34 |
CPU 115SER - Micro PLC 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 kHz outputs 32 kB work memory, 40 kB load memory RS485 interface |
[Datasheet] [Manual] |
Изделие: 114-6BJ03
16 (20) входов, 8 (4) выходов, 24 кбайт рабочей памяти, 32 кбайт загрузочной памяти, расширяемый
Изделие: 115-6BL34
16 (20) входов, 16 (12) выходов, 32 кбайт рабочей памяти, 40 кбайт загрузочной памяти, 2-й интерфейс RS-485 (PtP), расширяемый
Изделие: 114-6BJ52
16 входов, 8 релейных выходов (230 В перем. тока/30 В пост. тока), 16 кбайт рабочей памяти, 24 кбайт загрузочной памяти, расширяемый
Изделие: 115-6BL33
16 (20) входов, 16 (12) выходов, 24 кбайт рабочей памяти, 32 кбайт загрузочной памяти, 2-й интерфейс RS-485 (PtP), расширяемый