Модуль аналогового ввода, 2 изолированных канала, 12 разрядов, входной диапазон 0/4–20 мА, 2/3-проводная схема подключения
|
Наименование
|
Модуль аналоговых входов SM 031, AI 2x12Bit, 4...20 mA, 2/3 wire |
|
Тип
|
031-1BB10 |
|
Габаритные размеры, В х Ш х Г, мм
|
12.9 mm x 109 mm x 76.5 mm |
|
Температура окружающей среды
|
0 °C ... 60 °C |
|
Количество входов
|
2 |
|
Тип входного сигнала
|
0/4...20 mA |
![]() |
|
Status indication
![]() |
RUN | MF | AI x | Description |
| green | red | red |
|
|
| ● | ○ | X | Bus communication is OK Module status is OK |
|
| ● | ● | X |
Bus communication is OK |
|
| ○ | ● | X |
Bus communication is not possible |
|
| ○ | ○ | X | Error at bus power supply | |
| X | B | X |
Error in configuration |
|
| ● | ○ | ● |
Error channel x
|
|
| on: ● | off: ○ | blinks with 2Hz: B | not relevant: X | ||||
Pin assignment
| PM - Power module | Pos. | Function |
Type |
Description | |
![]() |
1 | +AI 0 | I | + Channel 0 | |
| 2 | 24V_ISO_0 | O |
DC 24V encoder supply Channel 0 |
||
| 3 | 0V_ISO_0 | O |
Ground channel 0 |
||
| 4 | FE | --- | Shield | ||
| 5 | +AI 1 | I | + Channel 1 | ||
| 6 | 24V_ISO_1 | O |
DC 24V encoder supply Channel 1 |
||
| 7 | 0V_ISO_1 | O |
Ground Channel 1 |
||
| 8 | FE | --- | Shield |
I: Input, O: Output
Order no. |
031-1BB10 |
| Type | SM 031 |
| Module ID | 0411 1543 |
General information |
|
| Note | - |
| Features | 2 inputs 12Bit Current 4...20 mA 2 wire |
Current consumption/power loss |
|
| Current consumption from backplane bus | 50 mA |
| Power loss | 0.7 W |
Technical data analog inputs |
|
| Number of inputs | 2 |
| Cable length, shielded | 200 m |
| Rated load voltage | DC 24 V |
| Current consumption from load voltage L+ (without load) | 20 mA |
| Voltage inputs | - |
| Min. input resistance (voltage range) | - |
| Input voltage ranges | - |
| Operational limit of voltage ranges | - |
| Operational limit of voltage ranges with SFU | - |
| Basic error limit voltage ranges | - |
| Basic error limit voltage ranges with SFU | - |
| Destruction limit current | - |
| Current inputs | ![]() |
| Max. input resistance (current range) | 60 Ω |
| Input current ranges | +4 mA ... +20 mA 0 mA ... +20 mA |
| Operational limit of current ranges | +/-0.5% |
| Operational limit of current ranges with SFU | - |
| Basic error limit current ranges | +/-0.3% |
| Radical error limit current ranges with SFU | - |
| Destruction limit current inputs (voltage) | - |
| Destruction limit current inputs (electrical current) | - |
| Resistance inputs | - |
| Resistance ranges | - |
| Operational limit of resistor ranges | - |
| Operational limit of resistor ranges with SFU | - |
| Basic error limit | - |
| Basic error limit with SFU | - |
| Destruction limit resistance inputs | - |
| Resistance thermometer inputs | - |
| Resistance thermometer ranges | - |
| Operational limit of resistance thermometer ranges | - |
| Operational limit of resistance thermometer ranges with SFU | - |
| Basic error limit thermoresistor ranges | - |
| Operational limit of resistance thermometer ranges with SFU | - |
| Destruction limit resistance thermometer inputs | - |
| Thermocouple inputs | - |
| Thermocouple ranges | - |
| Operational limit of thermocouple ranges | - |
| Operational limit of thermocouple ranges with SFU | - |
| Basic error limit thermoelement ranges | - |
| Basic error limit thermoelement ranges with SFU | - |
| Destruction limit thermocouple inputs | - |
| Programmable temperature compensation | - |
| External temperature compensation | - |
| Internal temperature compensation | - |
| Internal temperature compensation | - |
| Technical unit of temperature measurement | - |
| Resolution in bit | 12 |
| Measurement principle | successive approximation |
| Basic conversion time | 1.15 ms all channels |
| Noise suppression for frequency | >80dB (UCM<20V) |
Status information, alarms, diagnostics |
|
| Status display | yes |
| Interrupts | yes, parameterizable |
| Process alarm | yes, parameterizable |
| Diagnostic interrupt | yes, parameterizable |
| Diagnostic functions | yes |
| Diagnostics information read-out | possible |
| Module state | green LED |
| Module error display | red LED |
| Channel error display | red LED per channel |
Isolation |
|
| Between channels | ![]() |
| Between channels of groups to | 1 |
| Between channels and backplane bus | ![]() |
| Between channels and power supply | ![]() |
| Max. potential difference between circuits | DC 75 V/ AC 60 V |
| Max. potential difference between inputs (Ucm) | DC 75 V/ AC 60 V |
| Max. potential difference between Mana and Mintern (Uiso) | - |
| Max. potential difference between inputs and Mana (Ucm) | DC 75 V/ AC 60 V |
| Max. potential difference between inputs and Mintern (Uiso) | DC 75 V/ AC 60 V |
| Max. potential difference between Mintern and outputs | - |
| Insulation tested with | DC 500 V |
Datasizes |
|
| Input bytes | 4 |
| Output bytes | 0 |
| Parameter bytes | 20 |
| Diagnostic bytes | 20 |
Housing |
|
| Material | PPE / PPE GF10 |
| Mounting | Profile rail 35 mm |
Mechanical data |
|
| Dimensions (WxHxD) | 12.9 mm x 109 mm x 76.5 mm |
| Weight | 60 g |
Environmental conditions |
|
| Operating temperature | 0 °C to 60 °C |
| Storage temperature | -25 °C to 70 °C |
Certifications |
|
| UL508 certification | yes |
| Order no. | Name/Description | |
|---|---|---|
|
031-1BB10 |
SM 031 - Analog input 2 inputs 12Bit Current 0(4)...20mA 2 wire |
|
|
031-1BB30 |
SM 031 - Analog input 2 inputs 12Bit Voltage 0...10 V |
|
|
031-1BB40 |
SM 031 - Analog input 2 inputs 12Bit Current 0(4)...20 mA |
|
|
031-1BB60 |
SM 031 - Analog input 2 inputs 12Bit Current 0(4)...20mA 2 wire |
|
|
031-1BB70 |
SM 031 - Analog input 2 inputs 12Bit Voltage -10 V...+10 V |
|
|
031-1BB90 |
SM 031 - Analog input 2 inputs 16Bit Thermocouple type J, K, N, R, S, T, B, C, E, L Voltage -80mV...+80mV |
|
|
031-1BD30 |
SM 031 - Analog input 4 inputs 12Bit Voltage 0...10 V |
|
|
031-1BD40 |
SM 031 - Analog input 4 inputs 12Bit Current 0(4)...20 mA |
|
|
031-1BD70 |
SM 031 - Analog input 4 inputs 12Bit Voltage -10 V...+10 V |
|
|
031-1BD80 |
SM 031 - Analog input 4 inputs 16Bit 0 .. 3000 ohm resistance Resistance measurement with 2, 3, and 4-wires |
|
|
031-1BF60 |
SM 031 - Analog input 8 inputs 12Bit Current 0(4)...20mA 2 wire |
|
|
031-1BF74 |
SM 031 - Analog input 8 inputs 12Bit Voltage -10 V...+10 V |
|
|
031-1CA20 |
SM 031 - Analog input Direct connection of a resistor full bridge (DMS) or load cell 4- or 6-wire measurement 16 (24)Bit resolution Auto/self calibration zero point and final value Absolute exactness radical error ±0,1% (± 0,01%) Onboard power supply 2V5, 5V, 7V5, 10V and 12V |
|
|
031-1CB30 |
SM 031 - Analog input 2 inputs 16Bit Voltage 0...10 V |
|
|
031-1CB40 |
SM 031 - Analog input 2 inputs 16Bit Current 0(4)...20 mA |
|
|
031-1CB70 |
SM 031 - Analog input 2 inputs 16Bit Voltage -10 V...+10 V |
|
|
031-1CD30 |
SM 031 - Analog input 4 inputs 16Bit Voltage 0...10 V |
|
|
031-1CD35 |
SM 031 - Analog input 4 inputs 16Bit Voltage 0...10 V |
|
|
031-1CD40 |
SM 031 - Analog input 4 inputs 16Bit Current 0(4)...20 mA |
|
|
031-1CD45 |
SM 031 - Analog input 4 inputs 16Bit Current 0(4)...20 mA |
|
|
031-1CD70 |
SM 031 - Analog input 4 inputs 16Bit Voltage -10 V...+10 V |
|
|
031-1LB90 |
SM 031 - Analog input 2 inputs 16Bit Thermocouple Voltage -80mV...+80mV requires less parameter bytes than module 031-1BB90 |
|
|
031-1LD80 |
SM 031 - Analog input 4 inputs 16Bit 0 .. 3000 ohm resistance Resistance measurement with 2, 3, and 4-wires requires less parameter bytes than module 031-1BD80 |
|
|
032-1BB30 |
SM 032 - Analog output 2 outputs 12Bit Voltage 0...10 V |
|
|
032-1BB40 |
SM 032 - Analog output 2 outputs 12Bit Current 0(4)...20 mA |
|
|
032-1BB70 |
SM 032 - Analog output 2 outputs 12Bit Voltage -10 V...+10 V |
|
|
032-1BD30 |
SM 032 - Analog output 4 outputs 12Bit Voltage 0...10 V |
|
|
032-1BD40 |
SM 032 - Analog output 4 outputs 12Bit Current 0(4)...20mA |
|
|
032-1BD70 |
SM 032 - Analog output 4 outputs 12Bit Voltage -10 V...+10 V |
|
|
032-1CB30 |
SM 032 - Analog output 2 outputs 16Bit Voltage 0...10 V |
|
|
032-1CB40 |
SM 032 - Analog output 2 outputs 16Bit Current 0(4)...20 mA |
|
|
032-1CB70 |
SM 032 - Analog output 2 outputs 16Bit Voltage -10 V...+10 V |
|
|
032-1CD30 |
SM 032 - Analog output 4 outputs 16Bit Voltage 0...10 V |
|
|
032-1CD40 |
SM 032 - Analog output 4 outputs 16Bit Current 0(4)...20mA |
|
|
032-1CD70 |
SM 032 - Analog output 4 outputs 16Bit Voltage -10 V...+10 V |
|
|
031-1PA00 |
Energy measurement terminal 1/3 phase 230/400V 1A Resolution measured value |
|
Изделие: 031-1BB30
2 канала, 12 разрядов, входной диапазон 0…10 В
Изделие: 031-1CB70
2 канала, 16 разрядов, входной диапазон ±10 В
Изделие: 031-1CA20
Модуль аналогового ввода, 1 канал для подключения тензометрического датчика по 4- и 6-проводной схеме, разрешение 16 (24) разряда, авто и самокалибровка
Изделие: 031-1CD45
4 канала, 16 разрядов, входной диапазон 0/4–20 мА, сокращенный набор конфигурируемых параметров